| Titel:
|
Distribution of Evaporating CO2 in Parallel Microchannels |
| Type:
|
Article in proceedingsArticle in proceedings |
| Person(er):
|
Technical University of Denmark
Email:
Technical University of Denmark
Email:
|
| Uddrag:
|
The impact on the heat exchanger performance due to maldistribution of evaporating CO2 in parallel channels is
investigated numerically. A 1D steady state simulation model of a microchannel evaporator is built using correlations
from the literature to calculate frictional pressure drop and heat transfer coefficients. For two channels in
parallel two different cases of maldistribution are studied. Firstly, the impact of a non-uniform air flow is considered,
and secondly the impact of maldistribution of the two phases in the inlet manifold is investigated. The
results for both cases are compared to results obtained using R134a as refrigerant, and it is found that the performance
of the evaporator using CO2 is less affected by the maldistribution than the evaporator using R134a as
refrigerant. For both cases studied, the impact of the maldistribution was very small for CO2. |
| Publiceret:
|
part of: Proceedings of 8th IIR Gustav Lorentzen Conference on Natural Working Fluids (ISBN: 978-2-913149-63-2), 2008, |
| Præsenteret ved:
|
8th IIR Gustav Lorentzen Conference on Natural Working Fluids, Copenhagen |
|